Rotary Screw Compressor - No Control Air Supply
You're here because you discovered there's no control air available at the separator vessel outlet (or at the solenoid inlet).
This means one of two things:
- Minimum Pressure Valve (MPV) is leaking - Air escapes faster than it can build up
- Bypass hole in inlet valve is plugged - No air enters the compressor to build unload pressure
These are the harder diagnostics because:
- Checking internal pressure requires gauge installation (not always easy)
- MPV leakage is hard to detect when compressor is connected to piping
- Bypass hole may require inlet valve disassembly
But let's work through it systematically.
Background: How Control Air Is Generated
Before we troubleshoot, here's how control air is created:
Step 1: Small Bypass Hole
- Inlet valve has a small bypass hole (1-3mm diameter)
- Even when inlet valve is closed, this hole allows a tiny amount of air to enter
- This is intentional
Step 2: Build Unload Pressure
- That small airflow gradually builds up pressure inside the separator vessel
- Target unload pressure: 2.5-3.5 bar (35-50 PSI)
- This takes 10-30 seconds after startup
Step 3: Minimum Pressure Valve Holds It
- MPV only opens when pressure reaches 2.5-4 bar (depends on model)
- Below that, MPV stays closed
- This traps the unload pressure inside the separator
Step 4: Use It as Control Air
- This trapped unload pressure becomes your control air supply
- Feeds the solenoid, which directs it to the inlet valve when loading
When this fails:
- Either bypass hole is plugged (no air enters) → can't build pressure
- Or MPV is leaking (air escapes) → can't maintain pressure
Diagnostic Approach
Here's the practical way to narrow it down:
Check 1: Is There ANY Pressure Inside the Separator?
If you can easily check internal pressure (gauge on compressor, or Elektronikon display), this tells you a lot:
Internal pressure during unload running:
- Normal: 2.5-3.5 bar (35-50 PSI)
- Too low: 0-1 bar (0-15 PSI)
If pressure is low or zero:
- Either bypass hole plugged OR MPV leaking
- Go to Check 2
If pressure is normal (2.5-3.5 bar):
- Wait... that doesn't make sense. If internal pressure is normal, control air should be available.
- Double-check: Is the line from separator to solenoid actually connected? Plugged?
Check 2: Listen/Feel at the MPV
Note: This is easier if you can isolate the compressor from the piping system (close downstream isolation valve). If you can't do that, this check is much harder.
If you CAN isolate the compressor:
- Close downstream isolation valve (so system pressure = 0 bar)
- Run compressor in unload mode (it should build unload pressure if bypass hole is working)
- Listen/feel at the MPV outlet
- Is air leaking out?
- Should be NONE or very minimal leakage
If air is leaking:
- MPV is leaking
- Internal pressure can't build because air escapes
- Solution: Replace MPV valve kit ($50-$300)
If NO air leaking:
- MPV is holding pressure
- Problem is likely bypass hole plugged → Go to Check 3
If you CANNOT isolate the compressor (hardwired to piping with no isolation valve):
This is much harder. Piping pressure may be higher than internal pressure, so you won't detect MPV leakage (backflow prevents it).
Options:
- Temporarily disconnect compressor from piping (if feasible) - big job, often not practical
- Skip MPV test and go straight to checking bypass hole
- Try a "force test": Close vent valve on separator top (if equipped) - does internal pressure build now?
- ⚠️ Warning: Don't run long like this - you're pressurizing the separator without proper venting
Check 3: Check Bypass Hole in Inlet Valve
The bypass hole is critical but often overlooked.
What it is:
- Small hole or passage in the inlet valve (1-3mm diameter)
- Allows a small amount of air to enter even when inlet valve is closed
- Sometimes it's a drilled hole, sometimes an adjustable needle valve, sometimes an internal bypass channel
Problem:
- Gets plugged with dirt from intake air
- Especially common if intake air filter is dirty or damaged
How to check:
This varies by compressor model. Here are the common scenarios:
Option A: Visible Bypass Hole
- Remove intake air filter housing
- Look at the inlet valve from the intake side
- Look for a small hole drilled through the valve body or piston
- Try passing a thin wire through it (carefully - don't enlarge it!)
- Shine a light through it
Option B: Adjustable Needle Valve
- Some compressors have a small adjustable needle valve as the bypass
- Usually mounted on the inlet valve housing
- Check if it's closed (should be slightly open)
Option C: Internal Bypass Channel
- Some inlet valves have an internal bypass passage
- Not visible from outside
- May require partial disassembly to inspect
If bypass hole is plugged:
- Clean it carefully (don't enlarge the hole!)
- Use compressed air to blow through it (reverse direction)
- Check/replace intake air filter (that's usually why it plugged)
Check 4: Intake Air Filter
Often overlooked: A completely clogged intake air filter can also prevent air from entering.
How to check:
- Remove intake air filter
- Try to blow through it (should have airflow)
- Look at cleanliness (should be clean, not black/brown/caked with dirt)
If filter is clogged:
- Replace it immediately
- This may have also plugged the bypass hole → check bypass hole too
Typical replacement interval: Every 2,000-4,000 hours (sooner in dusty environments)
Real-World Cases
Case 1: Atlas Copco GA200 - Delta-P Reading Indicates Problem
Symptoms:
- Internal pressure 0.1 bar (essentially zero)
- Solenoid replaced, MPV serviced - no change
- Key clue: Delta-P air filter reading was 0.025 bar BEFORE start and didn't change after starting
Diagnosis:
- Delta-P across air filter should be near zero when compressor isn't running
- Reading 0.025 bar before start = something is wrong with sensor OR filter is completely clogged
- Reading doesn't change when running = no air is flowing
Root cause: Clogged intake air filter → bypass hole couldn't let air in → no unload pressure
Solution: Replace air filter, check bypass hole
Case 2: Atlas Copco (Unknown Model) - No Pilot Air
Symptoms:
- Inlet valve won't open
- Solenoid works OK
- No pilot air (control air) anywhere
Diagnosis: No control air supply
Troubleshooting approach:
- Check if there's any pressure in separator during unload running
- If YES: MPV leaking
- If NO: Bypass hole plugged or intake filter completely blocked
Common outcome: Usually bypass hole plugged due to neglected air filter maintenance
The Challenge: Diagnosing MPV vs Bypass Hole
Here's the honest truth: It's often hard to tell which one without some disassembly or testing.
Clues that point to MPV leaking:
- You CAN hear air venting somewhere (but shouldn't be)
- Previous MPV problems or old MPV
- Compressor has high hours (MPV valve seat wears out)
Clues that point to bypass hole plugged:
- Dirty or neglected intake air filter
- Compressor operated in dusty environment
- Recent maintenance where air filter was disturbed
Practical approach if you can't isolate the compressor:
- Start with the easier fix: Replace intake air filter first (it's due anyway)
- Check bypass hole if accessible
- If those don't fix it: Plan to replace MPV during next maintenance shutdown
Why this order?
- Air filter is cheap ($20-$80) and easy
- Bypass hole check depends on compressor design (may or may not be easy)
- MPV is more expensive ($50-$300) and you want to be sure before replacing
Temporary Workarounds (Not Permanent Solutions!)
If you need to keep the compressor running while waiting for parts or maintenance shutdown:
Workaround 1: Supply External Control Air
- Use shop air or another compressor
- Connect to the control air line (at solenoid inlet)
- Regulate to 3-4 bar (40-60 PSI)
- ⚠️ This works but is NOT a permanent solution - fix the root cause
Workaround 2: Force MPV Open
- If MPV is stuck closed (not leaking, just stuck)
- Some MPVs can be manually opened or adjusted
- ⚠️ Dangerous if system pressure is high - consult service manual
These are emergency measures only. Fix the actual problem as soon as possible.
Preventive Maintenance
Here's how to prevent "no control air" problems:
Every 2,000-4,000 Hours:
- Replace intake air filter - This is critical!
- Dirty filter is the #1 cause of plugged bypass holes
Every 8,000-16,000 Hours:
- Service or replace MPV
- Inspect valve seat, replace valve kit
- Cost: $50-$300 depending on size
Every 16,000-24,000 Hours:
- Service inlet valve
- Clean bypass hole (if accessible)
- Replace seals and actuator parts
Immediately If:
- Compressor operates in dusty environment → more frequent air filter changes (every 1,000-2,000 hours)
When to Call for Help
These diagnostics require mechanical knowledge and sometimes compressor disassembly.
Call a technician if:
- You can't access bypass hole without major disassembly
- You're not sure how to safely isolate compressor from piping
- MPV replacement requires special tools or procedures
- You're not comfortable working with compressed air systems
Typical service call: $300-$800 (includes diagnostics and parts)
Recommended Resources
In-Depth Training:
- Industrial Compressed Air Systems Course - comprehensive training covering rotary screw internal components, MPV function, inlet valve operation, and maintenance procedures
Related Troubleshooting:
- Main "Won't Load" Troubleshooting - start here
- Control Air Supply Chain Problems - solenoid and electrical issues
Summary Checklist
- Check intake air filter - Is it clogged? Replace if dirty
- Check bypass hole (if accessible) - Is it plugged? Clean carefully
- Check MPV for leakage (if you can isolate compressor) - Is air escaping? Replace valve kit
- Check internal pressure (if gauge available) - Should be 2.5-3.5 bar during unload running
Bottom Line
No control air supply comes down to two causes:
1. Bypass hole plugged (50%)
- Usually due to dirty intake air filter
- Fix: Replace filter, clean bypass hole
2. MPV leaking (50%)
- Worn valve seat, weak spring
- Fix: Replace MPV valve kit
Start with the easy stuff:
- Replace air filter
- Check bypass hole (if accessible)
- If those don't fix it → MPV is probably leaking
The challenge is that checking MPV is hard when compressor is connected to piping. If you can't isolate it, you may need to schedule a maintenance shutdown to properly diagnose and replace MPV.
Good luck! Let me know in the Q&A forum if you found the problem.