The pipes are too small for the airflow. Pressure at the compressor is fine but drops significantly by the time it reaches the point of use.
What you'll see
Verify there are no clogged filters or closed valves between the compressor and the point of use causing an artificial restriction.
How to diagnose
-
Measure pressure at compressor and at point of use
Install gauges at both ends. Run the system at normal demand. The difference is your pressure drop. Modern target: maximum 0.1 bar total. Old standard: maximum 0.7 bar (10%). If yours is above 1 bar, the piping is too small.
Result: Large drop from compressor to point of use = piping problem.
How to fix it
-
Upgrade to larger piping
Replace undersized sections with larger diameter pipe. Install the main header as a ring/loop so air reaches every point from two directions -- this effectively halves the pipe length and dramatically reduces pressure drop.
Don't increase compressor pressure to compensate for piping losses. You're spending energy to push air through a restriction. Fix the restriction instead.
Larger piping. Pressure gauges for before/after measurements.
This issue can also cause
- High Energy Use Excessive power consumption or unexpectedly high electricity bills, often caused by control problems, air leak...