Ahmad Jan : Project Engineer Marine services Company Ltd Jeddah. February 13, 2018 1 Answer
Question
Cooling system required for ( Atlas Copco ZR55-9-60-P Rotary Screw Air Compressors ) Air inlet temperature = 50 deg C Inlet pressure = 3.0 barg Pressure drop = 0.17 kpa Compressed air flow rate=260 cu.m /hr. Site Conditions: B. Climatic Conditions-Air Temperatures Range of monthly maximum 35.1 to 60.0 C Range of monthly minimum 6.0 to 12.00 C Range of monthly mean daily maximum 25.5 to 35.90 C Range of monthly mean daily minimum 12.3 to 26.00 C. Relative Humidity Maximum relative humidity 100% Minimum relative humidity 6% D. 1.5.3 General data from available records: Annual Rainfall (erratic) Average of 100 mm Wettest Months December through March Driest Months April through November Wind Velocity Maximum of 135 km/hr Velocity and Exposure Class C (carrying sand and dust) Seismic Classification Zone 2A Longitude 38.2275 ° E Latitude 23.9994 ° N Location: KSA Royal Commission/Jeddah

1 Answer

Expert 7 years ago

Hi,
You can find the cooling water requirements in the compressor manual.

For the ZR55 I found the following:

Cooling water inlet water temp = below 35 degrees Celsius

Cooling water outlet temp = below 50 degrees Celsius.

Max. cooling water pressure = 7 bar

I also found that for a dT (temp difference) of 15 degrees, the compressor needs a cooling water flow of 0.8 l/s (liters per second ).

Make sure the water is clean, no acids, etc.

All the best,

Cas